Cleaning Chemicals
Cleaning Chemicals
In many cases, RO elements can be effectively
cleaned with a high pH sodium hydroxide solution (NaOH) followed by a low pH
citric acid/HCl solution. The common chelating agent, EDTA, can be add to the
sodium hydroxide solution if necessary.
Cleaning Procedure:
1. Flush all vessels with
RO permeate until the feed-concentrate process water is completely displaced.
2. Prepare a high pH NaOH
solution per the allowable pH and temperature guidelines.
3. Introduce cleaning
solution at a rate of 75 l/min per 8-inch diameter vessel.
4. Recirculate the
cleaning solution at a rate of 151 l/min per 8-inch diameter vessel for a
period of 45 minutes.
5. Allow solution to soak
if it has been determined that an extended soak time is beneficial to the
cleaning process. Extended soak times typically range from 1-12 hours.
6. Flush the high pH
cleaning solution from the vessels using RO permeate until the flush water pH
exiting the vessel is close to the flush water pH entering the vessel.
7. Closely monitor the pH
of the cleaning solution during the cleaning process and adjust the pH as
needed.
8. Measure the
temperature and flow of the cleaning solution during the start, middle and end
of the recirculation periods.
9. Never allow the vessel
pressure drop to exceed 4 bar (60 psi) during any point in the cleaning.
10. Proceed with a low pH cleaning using
citric acid. HCl or the combination of Citric Acid and HCl can be used for
making the low pH cleaning solution.
11. Once the low pH cleaning is complete,
flush the spent solution from the vessels using RO permeate until the flush
water pH exiting the vessel is close to the flush water pH entering the vessel.
12. Cleaning chemicals may be present in
the permeate after cleaning. Upon restart (post-cleaning), RO permeate should
be directed to drain for a minimum of 10 minutes. Please note that the permeate
conductivity is usually elevated after a cleaning and may take some time to
stabilize.